Live demo · simulated data from a fictional plant. Values update every second. Back to uptika.eu
PNPlant NorthWaste-to-energy · demo site

Overview

--:--:-- 1

IR-01 · Waste bunker · 6 regions

Live thermal image of the selected camera
LIVEIR-01 · 640×480 · 9 Hz · ε 0.95
Optical cameraYour visible-light camera of the same area appears here.
10 °C90 °C
iron · auto span

Measuring regions

RegionCameraMax °CTrend 60 minRise °C/minΔT KHot areaStatus

Early-warning logic

Limits per region · editable in Settings
  1. NormalAll indicators inside limitsLogged every second
  2. WatchRise > 2 °C/min or ΔT > 15 KHighlighted on dashboard
  3. Pre-alarm> 60 °C for 60 s or ΔT > 20 KPush to control room
  4. Alarm> 70 °C or rise > 5 °C/minSMS + call · relay output
  5. ResolvedBack inside limits for 15 minAcknowledged · report filed

Region B1

Alarm
Bunker, far left · IR-01
HOTSPOT NOW
78.4°C
▲ +6.2 °C/min
−60 min−30 minnow

    Rate of rise flagged B1 9 min before the temperature limit was reached.

    Risk indicators

    B1

    Automated response

      Event log

      today

        System health

        checked 09:42
        Cameras4 / 4 online
        Frame rate9 Hz on all
        Lens checkIR-03 light dust
        GatewayLAN + 4G · 1 s
        RelaysR2 active
        Storage92 days kept